This article details how to configure the LoRa Network. This will allow Nube-iO controllers, that are equipped with LoRa (RAW) radio cards, to act as Wireless LoRa (RAW) Gateways to receive data from Wireless LoRa Sensors.
Navigate to `SERIAL NETWORKS` Settings
Select 'Driver > LoRa Network' from the Rubix Platform Sidebar; Next select the `SERIAL NETWORKS` tab. Here you will see the LoRa Network settings.
It is essential that the `SERIAL NETWORKS` settings are correctly configured for the LoRa Gateway to operate. The `SERIAL NETWORKS` settings should be configured with values as follows:
Port: /data/socat/loRa1 (for a Rubix Compute 5)
Baud Rate: 38400
Stop Bits: 1
Parity: N
Byte Size: 8
Timeout: 5
The `SERIAL NETWORKS` settings should match the image below: